Operating Manual SG Series 10 –20 – 30 - 40 kVA

Code

Alarms

Meaning

4700

DC LOW

Battery voltage is at the lowest limit.
Will stay Off Inverter until the battery voltage reaches the value
in parameter.

4900

LOAD LOCKED

ON INVERTER

The Load is locked on Inverter after 3 Load transfers within 30
seconds.
After time out (default 30 seconds) Bypass will be free.

4955

OVERTEMPERATURE

An over-temperature condition has been detected on Inverter.
Elapsed “stop operation” time, Inverter shutdown.
With Utility OK, Load is transferred on Utility.

4998

LOAD OFF DUE TO

EXTENT. OVERLOAD

Load Off after time-out of “stop operation” for overload on
Inverter or Bypass (time depending on the % of overload).

4999

LOAD OFF DUE

TO UBATT. OR TEMP.

Load Off after time-out of “stop operation” with missing Utility
due to Battery low voltage or over-temperature condition.