Page 39/83

OPM_SGS_USM_10K_40K_0US_V030.doc

Operating Manual SG Series 10 –20 – 30 - 40 kVA

6.6.2 Messages list

Code

Message

Meaning

4002

WATCHDOG

RESET

The microprocessor has detected an incorrect operation:
Transfers the Load on Utility and performs a program reset.
The Inverter will restart automatically and will supply the Load.

4111

RECTIFIER

UTILITY OK

Rectifier Input Utility is again within the admitted tolerance
(voltage, frequency and phase).

4119

BATTERY TEST

STARTED

Start of Manual or Automatic Battery Test.

4120

BATTERY TEST

STOPPED

End of Manual or Automatic Battery Test.

4161

RECTIFIER

ON

Rectifier started.

4162

RECTIFIER

OFF

Rectifier shutdown.

4163

GENERATOR

ON

Customer Interface Board (X1 - 11, 22) received a Gen-set ON
signal.
Operating mode depend on setting of Parameters.

4164

GENERATOR

OFF

Customer Interface Board (X1 - 11, 22) received a Gen-set OFF
signal.
Function Bypass enabled depends on setting of parameter.

4302

INVERTER

CANNOT BE

TURNED ON

Inverter cannot be switched on because one of the following
conditions is still present:

Over Temperature

Low Battery Voltage

Inverter Fuses

Overload

K7 opening Failure

High Battery Voltage

DC Low

EPO

4303

INVERTER

CANNOT BE

TURNED OFF

Inverter cannot be switched OFF, because the Load cannot be
switched to Utility (voltage out of tolerance, not synchrony, BP
blocked).

4361

INVERTER

ON

The command to start the Inverter has been activated on the
control panel.

4362

INVERTER

OFF

The command to switch OFF the Inverter has been activated by
the control panel or automatically for alarm presence.

4411

BYPASS UTILITY

OK

Bypass Input Utility is again within tolerance (voltage, frequency
and phase).

4500

COMMAND

LOAD OFF

Disconnection of the Load by opening K6 and K7 for:
EPO / total off / Overload / stop operation.

4521

NO BYPASS

POWER

With the Load supplied by Automatic Bypass, a Utility Failure or
K6 opening occurred.

4534

MULTIPLE LOAD

TRANSFER

2 transfers Inverter- Utility have been detected in a short time,
(default 30 seconds).

4535

BYPASS

LOCKED

Bypass is not available.
Contactor K6 and K8 are open, SSM deactivated.

4536

BYPASS

FREE

Bypass is enabled.
Contactor K6 is closed.