4 complete ups shutdown (no load supply), Complete ups shutdown (no load supply) – GE Industrial Solutions SG Series 10 – 20 – 30 – 40 kVA Operating Manual User Manual

Page 46

Advertising
background image

Modifications reserved

Page 46/83

OPM_SGS_USM_10K_40K_0US_V030.doc

Operating Manual SG Series 10 –20 – 30 - 40 kVA

7.1.4 Complete UPS shutdown (No Load supply)

NOTE !

The Load must be disconnected.


Initial status:

Load supplied from Inverter.

1. Press total off button.

Load is disconnected from UPS.
Rectifier is shut down and all output and

input contactors will be opened.

• LED’s, Rectifier, Inverter and Load are OFF.

2. Open Q1 (Pos. O).

LED service check lights up.

3. Disconnect the Battery from the UPS in case

of External Battery.
• Wait 5 minutes for DC-Link Capacitors

discharge.

4. Disconnect the Utility.

• All LED’s are OFF.

END OF PROCEDURE

Advertising