. repair, Repair – Burkert Type 8650 User Manual

Page 106

Advertising
background image

106

Fault

Possible.cause

Remedy

SF LED lights up.

Wrong configuration.

Use the corresponding module from the
hardware catalogue.

Valve diagnosis trips (short circuit,
open outlet port).

Check the proper installation of the valve.

Replace defective valves.

Deactivate the diagnosis for valve posi-
tions not in use.

Module does not start due to
internal current limit (short circuits at
the outlet ports).

Remedy the short circuits (defective
valves at the outlet ports)

Carry out a voltage reset of the module /
system.

If an ET200iSP station has started once with Profibus address X, the address can be changed as follows:

Switch off the station.

Set the address 0 (all DIP switches in position OFF).

Switch on the station and wait approx. 10 seconds.

Switch off the station and wait approx. 10 seconds again.

Set the desired new address Y.

Switch on the station.

The new address is stored.

3.4.

Repair

If a repair is necessary, send the module to your local Bürkert subsidiary or contact our After-Sales Service.

Address and telephone number can be found in the chapter „General Information / Scope of Supply“.

Type 8650

english

Maintenance and Repair

Advertising