Burkert Type 8650 User Manual

Page 91

Advertising
background image

91

2.5.4.

Parameters that can be displayed or modified by channels

Name

Value

Unit

Status

#.#.Channel.0
Channel enable

enable

-

Initial value

Behavior at CPU/Master-STOP

switching alternative value

Alternative value

0

#.#.#.Pilot.valve
Switching cycle counter reset

inactive

-

Initial value

ID number of the pilot valve

0

Initial value

Current number of the switching cycles

74766

-

#.#.#.Actuator
Enable switching cycle counter diagnosis

enable

-

Initial value

Switching cycle counter warning limit

0

Switching cycle counter reset

inactive

Date of the last switching cycle counter reset

-

Current number of switching cycles

74766

-

#.#.#.Diagnosis
Group diagnosis

barred

-

-

Broken wire
Short circuit

2.5.5.

Functions of the channel parameter (general)

• Enable.channel.(read./.write).

Defines whether or not the channel is enabled for use.

• Behavior.at.CPU/Master.STOP.(read./.write).

Defines which value the channel assumes when the master is set to STOP.

• Alternative.values.(read./.write).

Defines the alternative value for the case „Switch alternative value at master STOP“.

2.5.6.

Functions of the parameter actuator (that are connected to
the pilot valve (of this channel)

• Switching.cycle.counter.reset.

Initiates a reset of the actuator switching cycle counter.

• ID.number.of.the.pilot.valve.(read./.write)

.

You can enter the ID number of the pilot valve used here. This makes it quickly available if replacement or pre-
ventive maintenance are forthcoming.

• Current.number.of.switching.cycles.(read.only)

.

Indicates how many switching cycles the pilot valve has performed since the last counter reset.