1.3.

Field of Application

The AirLINE Ex System is designed for decentralized operation in industrial environments.
Thanks to the modular configuration, electronics and fluidics can be combined particularly simply and efficiently.
It complies with protection class IP30.

DANGER!

Risk.of.electric.shock!.

The terminal modules (with upright system wiring) are designed for the Ex-protection class “Ex-e” (increased
safety).

• Before working on the terminal modules, always switch off the operating voltage to the system.

Further information can be found in the handbook for the Siemens ET200iSP.

Danger.of.explosion!

If a system is installed in a control cabinet in the explosion-proof area, observe the following:

• The control cabinet must be authorized for use in the explosion-protected area.

• The control cabinet must be dimensioned large enough to ensure that the generated lost heat can be dissi-

pated to the exterior in a suitable manner.

• The internal temperature of the control cabinet must not exceed the max. permitted ambient temperature for

the device.

1.4.

Marking

Type 8650
Ident no. 001xxxxxx
Serial no. 00001123

Fig. 3:

Location of the type label

Fig. 4:

Type label

Information about the labeling of the electronic and terminal modules can be found in the chapters
Configuration and Function of the Modules / Terminal Module / Labeling and
Configuration and Function of the Modules / Electronic Module / Labeling.