Fig. 3: Adjustment of the angle of inclination

Fig. 4: Turning by fastening in the centre

4

.4 Instructions for installation

For tight installation of the version with plastic horn antenna with
compression or adapter flange, the following conditions must be
fulfilled:

1

Use suitable flat seal, e.g. of EPDM with Shore hardness 25 or 50

2

Make sure the number of flange screws corresponds to the
number of flange holes

3

Tighten all screws with the torque stated in the technical data

The emitted radar impulses of the radar sensor are electromagnetic
waves. The polarisation plane is the direction of the electrical wave
component. By turning the instrument in the connection flange or
mounting boss, the polarisation can be used to reduce the effects of
false echoes.

The position of the polarisation plane is marked on the process fitting
of the instrument.

Tight installation of the
plastic horn antenna

Polarisation plane

12