4 electrical connection, Electrical connection – Cashco Siemens PS2 I/P User Manual

Page 48

Advertising
background image

Preparing for Operation

48

SIPART PS2 Manual

A5E00074631-01

3.4 Electrical Connection

.

NOTE
Any necessary options modules must be installed before electrical

connection (see chapter 2.5, page 25).
N.B.: The transmission ratio selector can only be set when the

positioner is open. Therefore check this setting before sealing the

controller.

!

WARNING
For the electrical installation, please observe the pertinent regulations,

in hazardous areas particularly the rules and regulations for the

installation and operation of systems in hazardous areas (e.g. in

Germany: Elex V, VDE 0165)
The explosion proof positioner may only be supplied with electrical

power in areas in which the atmosphere may be potentially explosive

when the housing is closed.
The feed--though openings in the explosion proof version for the

electronic connections must be sealed with EEX-d certified cable

glands or EEx-d certified plugs or an ignition lock must be mounted at

a maximum distance of 46 cm (18 inches) when using the

“conduit”-system.

The plastic housing is metal lined to increase the electromagnetic

compatibility (EMC) against high frequency radiation. This screen is

connected electrically to the threaded bushes shown in figure 3-11,

page 49.
Please bear in mind that this protection can only be effective if you con-

nect at least one of these bushes with grounded fittings by electrically

conductive (blank) mounting parts.