Preparing for Operation

66

SIPART PS2 Manual

A5E00074631-01

The following display appears after pressing the operation mode key

briefly:

To exit the Configuration mode, press the operation mode key

for

longer than 5 s. The software version is displayed after about 5 s. The

instrument is in manual operation after releasing the operation mode

key.

.

NOTE
You can abort an ongoing initialization at any time by pressing the ope-

ration mode key. Your previous settings are retained. All the parame-

ters are set to the factory setting only after performing a “Preset”.

3.6.6

Manual initialization of rotary actuators

The positioner can be initialized with this function without the actuator

being driven hard against the limit stop. The start and end positions of

the displacement path are set manually. The other initialization steps

(optimization of the control parameters) run automatically as in automa-

tic initialization.

1.

Make preparations as described in chapter 3.6.4, page 64 for

rotary actuators. In particular, make sure by manually driving the

whole displacement path that the displayed potentiometer setting

moves in the permissible range between P5.0 and P95.0.

2.

Press the operation mode key

for longer than 5 s. This brings

you to the Configuration mode.

Display:

3.

Set the parameter YFCT to “turn” with the decrement

key.

Display:

Manual initializa-

tion procedure in

rotary actuators