Cashco Siemens PS2 I/P User Manual

Page 88

Advertising
background image

Operation

88

SIPART PS2 Manual

A5E00074631-01

Limit value for monitoring the way integral
A limit value for the way integral can be set here. If the way integral

exceeds the limit value, the fault message output (optional) is activated.
This function enables a preventive maintenance of the fitting, see also

chapter 4.5 “Diagnostics”, page 90.
This monitoring function can be deactivated with the OFF setting

(factory setting).

Limit value for monitoring the change of direction
A limit value for the direction change counter can be set here. If this

counter exceeds the limit value, the fault message output is activated.
This function enables a preventive maintenance of the fitting, see also

chapter 4.5 “Diagnostics”, page 90.
This monitoring function can be deactivated with the OFF setting

(factory setting).

Tolerance value for monitoring the bottom hard stop
With this value a limit value (in percent related to the total mechanical

distance) can be preset for the monitoring of the bottom hard stop. If

this tolerance value is exceeded or dropped below of, the fault

message output (optional) is activated.
This function detects when the bottom stop has changed by more then

the specified tolerance related to its initialization value. Monitoring

takes place when the valve is in sealing bottom. Activation of the

sealing bottom function (parameter “39.YCLS”) is therefore a

prerequisite.
The fault message remains activated until either a subsequent

monitoring remains within the tolerance or a new initialization is

performed.
This monitoring function can be deactivated with the OFF setting

(factory setting). See also chapter 4.5 “Diagnostics”, page 90.

Tolerance value for monitoring the top hard stop
With this value a limit value (in percent related to the total mechanical

distance) can be preset for the monitoring of the top hard stop. If this

tolerance value is exceeded or dropped below of, the fault message

output (optional) is activated.
This function detects when the top stop has changed by more then the

specified tolerance related to its initialization value. Monitoring takes

place when the valve is in sealing top. Activation of the sealing top

function (parameter “39.YCLS”) is therefore a prerequisite.
The fault message remains activated until either a subsequent

monitoring remains within the tolerance or a new initialization is

performed.
This monitoring function can be deactivated with the OFF setting

(factory setting).

50. STRK

51. DCHG

52. ZERO

53. OPEN