Operation

77

SIPART PS2 Manual

A5E00074631-01

The display of the positioner shows you the current potentiometer

setting in the top line and ”NOINIT” flashes in the second line. You can
move the actuator with the decrement and increment key

. In order

to adapt the positioner to your actuator, you have to change to the

Configuration menu. See also chapter 3.6, page 57 “Commissioning”.
Output of alarms and position feedback is possible after successful in-

itialization.

To go to the Configuration menu, press the operation mode key

for

at least 5 seconds. In the Configuration menu you can adapt the

positioner individually to your actuator and start initialization. Only a few

parameters need to be set in the positioner prior to initialization. The

others are defaulted so that they do not normally need to be adjusted.

You can block the Configuration menu against manipulation by an

appropriately parameterized and activated digital input. Which

parameters you need to set and all other parameters are explained in

chapter 4.4, page78Parameterization.
The configuration mode can be reported by outputting a

parameterizable fault message, a position feedback or output of limit

values A1 and A2 is not possible.

.

NOTE
If the electric power supply fails during configuration, the positioner

switches back to the first parameter after recovering the power supply,

values which have already been parameterized are retained. Without a

power failure you re--enter the configuration menu at the point you

exited it when you call the Configuration menu again.

at the same time

at the same time

at the same time

at the same time

to

Figure 4-5

Overview: Configuration

P-manual mode

(ex--factory state)

Configuration and

initialization