Preparing for Operation

59

SIPART PS2 Manual

A5E00074631-01

3.6.2

Automatic initialization of linear actuator

If you can move the actuator correctly, leave it standing in a central po-

sition and start automatic initialization:

1. Press the operation mode key

for longer than 5 s. This brings

you to the Configuration operating mode.

Display:

2. Switch to the second parameter by pressing the operation mode

key

briefly.

Display:

or

.

NOTE
It is vital that this value corresponds to the setting of the transmission

ratio selector (8, figure 2-1, page 16) (33° or 90°).

3. Switch on to the following display with the operation mode key

:

You only need to set this parameter if you want to have the total

stroke in mm displayed at the end of the initialization phase. To do

this, select the same value in the display to which you have set the

carrier pin to the scale on the lever.

4. Switch on to the following display with the operation mode key

: