5 diagnosis, 1 diagnostic display, Diagnosis – Cashco Siemens PS2 I/P User Manual

Page 90: Diagnostic display, Operation 90

Advertising
background image

Operation

90

SIPART PS2 Manual

A5E00074631-01

4.5 Diagnosis

4.5.1 Diagnostic display

You go to the diagnostic display from automatic or manual operation by

simultaneously pressing all three keys for at least two seconds.
Table 3-1, page 91 shows an overview of the displayable values. In the

third column the corresponding English term from which the abbrevia-

tion is derived is shown next to the German meaning unless this is self

explanatory.
The diagnostic display has a similar structure to in the ”Configuration”

operating mode. the top line shows the value of the diagnostic variable,

the bottom line the number and abbreviation of the displayed variable.
The respective next diagnostic value can be selected with the operation
mode key

. By pressing and holding the operation mode key and

additionally pressing the decrement key

you can select the diagno-

stic values in reverse order.

Certain values can be set to zero by pressing the increment key

for

at least 5 seconds. This is noted in the last column in the table.
Some diagnostic values may be greater than 99999. In this case the

display switches to exponential display. Example: the value 1234567 is

displayed as 1.23E6.

No. Abbrevia-

tion

Meaning

Displayable

values

Unit

Rest

poss.

1

STRKS

Number of strokes (Strokes)

0 to 4.29E9

--

x

2

CHDIR

Changes of direction (Changes of Direction)

0 to 4.29E9

--

x

3

CNT

Fault counter (Counter )

0 to 4.29E9

--

x

4

A1CNT

Alarm counter 1 (Alarm 1 Counter)

0 to 4.29E9

--

x

5

A2CNT

Alarm counter 2 (Alarm 2 Counter)

0 to 4.29E9

6

HOURS

Operating hours (Hours)

0 to 4.29E9

Hours

7

WAY

Determined actuating path (Way)

0 to 130

mm or _

8

TUP

Travel time up (Travel Time Up)

0 to 1000

s

9

TDOWN

Travel time down (Travel Time Down)

0 to 1000

s

10

LEAK

Leakage (Leakage)

0.0 to 100.0

%

11

P0

Potentiometer value below stop (0%)

0.0 to 100.0

%

12

P100

Potentiometer value bottom stop (100%)

0.0 to 100.0

%

13

IMPUP

Impulse length up (Impulse Length Up)

2 to 100

ms

14

IMPDN

Impulse length down (Impulse Length Down)

2 to 100

ms

15

DBUP

Dead zone up (Dead Band Up)

0.1 to 100.0

%

16

DBDN

Dead zone down (Dead Band Down)

0.1 to 100.0

%

17

SSUP

Short step zone up (Short Step Zone Up)

0.1 to 100.0

%

18

SSDN

Short step zone down (Short Step Zone Down)

0.1 to 100.0

%

19

TEMP

Current temperature

--40 to 85

_

C

20

TMIN

Minimum temperature (”drag pointer”)

--40 to 85

_

C

21

TMAX

Maximum temperature (”drag pointer”)

--40 to 85

_

C

22

T1

Number of operating hours in Temperature range 1

0 to 4.29E9

Hours

23

T2

Number of operating hours in Temperature range 2

0 to 4.29E9

Hours

24

T3

Number of operating hours in Temperature range 3

0 to 4.29E9

Hours

25

T4

Number of operating hours in Temperature range 4

0 to 4.29E9

Hours

26

T5

Number of operating hours in Temperature range 5

0 to 4.29E9

Hours

27

T6

Number of operating hours in Temperature range 6

0 to 4.29E9

Hours