Cashco Siemens PS2 I/P User Manual

Page 84

Advertising
background image

Operation

84

SIPART PS2 Manual

A5E00074631-01

Setpoint vertex points (see figure 4-8, page 83)
A flow parameter can be assigned to the respective setpoint vertex va-

lue at an interval of 5%. These points lead to a polygon chain with 20

straight lines which therefore represents a projection of the valve cha-

racteristic.
The setpoint vertex values can only be input at You may only enter a

strictly monotonous characteristic, the vertex values of which differ by

at least 0.2%. If the monotony condition has been infringed, an error

message appears as soon as you want to exit ”Configuration”. If you

need a falling characteristic you have to enter a rising characteristic

and reverse the direction of action by entering 7.SDIR = fall.

Dead zone of the controller
At dEbA = AUto the dead zone in automatic operation is adapted conti-

nuously to the requirements of the control circuit. The dead zone is gra-

dually increased on detecting a control oscillation. The reverse adapta-

tion takes place by a time criterion.
In the other discrete settings the fixed value is used for the dead zone.

Manipulated variable limiting start (see figure 4-8 and 4-9)

and

Manipulated variable limiting end (see figure 4-8 and 4-9)
With the parameters “35.YA” and “36.YE” the mechanical actuating di-

stance (from stop to stop) is limited to the set values. In this way the

mechanical setting range of the actuator can be limited to the active

flow and the integral saturation of the commanding controller avoided.

Manipulated variable standardization (see figure 4-8 and 4-9)
With limiting of the manipulated variable (by “35.YA” and “36.YE”) two

different scalings are produced for the display and the position feed-

back via the current output (MPOS or FLOW).
The MPOS scaling shows the mechanical position (0 to 100%) bet-

ween the hard stops of the initialization. This is not affected by the pa-

rameters “35.YA” and “36.YE”. The parameters “35.YA” and “36.YE”

are displayed in the MPOS-scale.
The FLOW-scale is the standardization (0 to 100%) to the range bet-

ween “35.YA” and “36.YE”. The setpoint w (0 to 100%) is always refer-

red to this range. This gives (also by using valve characteristics) a

quasi--flow--proportional display and position feedback Iy.
To calculate the control difference, the setpoint is also shown in the ap-

propriate scale on the display.

13.SL0 to 33.SL20

34.DEBA

35.YA

36.YE

37.YNRM