Current temperature
Current temperature in the positioner housing The sensor is on the

electronics board.

Minimum temperature (drag pointer)

and

Maximum temperature (drag pointer)
The minimum and maximum temperature inside the housing is determi-

ned and stored continuously in a kind of drag pointer.

Number of operating hours in temperature range T1 to T9
Statistics how long operation takes place in which temperature ranges

is kept in the instrument. To do this, the measured temperature over

one hour respectively is averaged and incremented in the counter

which is assigned to the corresponding temperature range every hour.

This enables you to draw conclusions about the past operating condi-

tions and thus the whole fitting.
The temperature ranges are divided up as follows:

T1

T2

T3

T4

T5

T6

T7

T8

T9

Temperature

range [_C]

≥--30

≥--30

<--15

≥--15

< 0

≥0

< 15

≥15

< 30

≥30

< 45

≥45

< 60

≥60

< 75

≥75

Number of cycles pre--control valve 1

and

Number of cycles pre--control valve 2
These two counters add up the control processes of the pre--control

valves.

Store maintenance data

A store function is triggered by pressing the increment key

for at

least 5 seconds. Here the diagnostic data 7 to 17 are stored in a non--

volatile memory as ”Data of the last maintenance”. These diagnostic

data are selected values, the changes of which can provide information

on the mechanical wear of the valve.
Normally this function is operated via HART, e.g. with PDM, menu item

Instrument!Store maintenance info. It is possible to compare the data

of the last maintenance with the current data.

4.5.3 Online-Diagnosis

Some important variables and parameters are monitored continuously

during operation. In the “Configuration” operating mode you can confi-

gure this monitoring so that the fault message output is activated when

a certain event such as exceeding a limit value occurs.

19 TEMP

20 TMIN

21 TMAX

22 T1 to

30 T9

31 VENT1

32 VENT2

33 STORE