Operation

92

SIPART PS2 Manual

A5E00074631-01

Determined actuating way
This value indicates the actuating way determined during initialization

according to the display at the end of an initialization. Prerequisite in

linear actuator: Specification of the lever arm with the parameter

“3.YWAY”.

Travel time up

and

travel time down
These values show the travel times which have been determined du-

ring initialization. The unit is seconds.

Leakage
If a leakage message has been output during initialization, the value of

the leakage can be read here in %/min.

Potentiometer value bottom stop

and

Potentiometer value top stop
These two values indicate the measured values of displacement mea-

surement (potentiometer) at the bottom and top hard stops as determi-

ned in automatic initialization. In manual initialization the values of the

manually reached limit positions are indicated here.

Impulse length up

and

Impulse length down
During initialization the smallest impulse lengths are determined with

which a movement of the actuator can be achieved. They are determi-

ned and displayed here for the “Up”-direction and the “Down”-direction.

Dead zone up

and

Dead zone down
Here the dead zone of the controller is displayed in “Up”-direction or in

“Down”-direction. The values correspond either to the manually set va-

lue of the parameter“34.DEBA” or the value adapted automatically by

the instrument when “DEBA” has been set to ”Auto”.

Short step zone up

and

Short step zone down
The short step zone is the range of the controller in which pulse--sha-

ped control signals are output. The impulse length here is proportional

to the control error. If the control error is outside the short step zone,

the valves are controlled in continuous contact.

7 WAY

8 TUP

9 TDOWN

10 LEAK

11 P0

12 P100

13 IMPUP

14 IMPDN

15 DBUP

16 DBDN

17 SSUP

18 SSDN