The fault message remains activated until either a subsequent

monitoring remains within the tolerance or a new initialization is
performed. The deactivation of the monitoring (“52. ZERO”=OFF) also

clears any existing fault message.
This monitoring function supplies no useful results when the stops have

not been determined automatically in initialization but the limits set

manually (manual initialization“5.INITM”).
An appropriate diagnosis is made for the top hard stop. The limit value

for this is set with the parameter . Activation of the sealing top function

(parameter “39.YCLS”) is therefore a prerequisite.

8

Monitoring of the dead zone adaptation
If the dead zone increases unproportionally in operation in automatic

adaptation of the dead zone (parameter DEBA = Auto) this points to an

error in the system (e.g. a marked increase in stuffing box friction, play

in the displacement detection, leakage). Therefore a limit value can be

specified for this value (”54. DEBA”, limit value for dead zone

monitoring) which activates the fault message output when it is

exceeded.