Value for sealing bottom
When the sealing function bottom (see parameter“39.YCLS”is activa-

ted, it can be set below which setpoint the bottom sealing is activated

with this parameter.

Value for sealing top
When the sealing function top (see parameter“39.YCLS”is activated, it

can be set above which setpoint the top sealing is activated with this

parameter.

Function digital input 1 (see figure 4-6, page 79)

and

Function digital input 2 (see figure 4-6)
The parameters “42.BIN1” and “43.BIN2” can be set individually depen-

ding on the purpose. The direction of action can be adapted to an NCC

or an NOC.

-

BIN1 or BIN2 = on or --on
Digital messages of the periphery (e.g. pressure or temperature

switches) can be read out via the HART interface or lead to respon-

ding of the fault message output by OR linking with other messages.

-

BIN1 = bLc1
The Configuration operating level is locked to prevent it being adju-

sted (e.g. by a wire jumper between terminals 9 and 10).

-

BIN1 = bLc2
If digital input 1 has been activated, manual operation is also locked

in addition to the Configuration operating level.

-

BIN1 or BIN2 = uP or doWn (contact closes) or --uP or --doWn (con-

tact opens).
The actuator drives the linear actuator to the upper or lower stop

when the digital input is activated with continuous contact.

-

BIN1 or BIN2 (contact closes) = StoP or --StoP (contact opens).
With activated digital input the piezo--valves are blocked and the

actuator remains in the last position. Leakage messages can then

be executed without initialization function.

-

BIN1 or BIN2 = oFF (factory setting)
no function

special function of DI1: If the digital input 1 is activated in P manual

operation by a jumper between terminals 9 and 10, ”NOINI” or the

100times input current in mA is displayed alternately in the bottom

line of the display.

If one of the above named functions is selected with the parameters

“42.BIN1” and “43.BIN2” simultaneously, then “Blocking” has priority

over “Up” and “Up” priority over “Down”.

40.YCDO

41.YCUP

42.BIN1

43.BIN2