Controlled Products Systems Group 1834-080 User Manual

Page 65

Advertising
background image

6.1.4

Elevator Board / Floor Hardware Test

This testing sequence will allow you to check activation of individual relays on the elevator control
board(s) and will confirm communication between the telephone entry system circuit board and the
elevator control board(s).

1. Press *77 and enter the four-digit master code _ _ _ _ (beep).

The display will show: WHICH ELEVATOR? (1835 - 1837 systems only).

2. Enter the elevator shaft number (1, 2, 3 or 4) _ , then press * (beep).

The display will show: FLOOR? (1835 - 1837 systems only).

3. Enter the two-digit floor number _ _ , then press * (beep).

4. The relay LED on the elevator control board that represents the floor number entered will

turn ON for approximately 1 second.

5. To check other floor relays, repeat steps 2 and 3.

6. When complete with the testing, press 0# TOGETHER to end this testing sequence.

NOTE: This program test sequence will automatically end itself if no keypad inputs are
detected after approximately 30 seconds.

Refer to the Elevator Control board installation manual for more information on trouble
shooting the elevator control boards
.

6.1.5 Automatic

Hang-up

Options

This sequence will allow you to program different methods by which the telephone entry system will
hang-up if a resident denies a guest access by hanging up their telephone rather than pressing the #
key to terminate the call.

Factory setting is 1, dial tone detect ON.

1. Press *40 and enter the four-digit master code _ _ _ _ (beep).

The display will show: 0=N 1=DT 2=SIL 3=BTH (1834, 1835, 1837 systems only).
0 – BOTH OFF. Unit hangs up after programmed strike time runs out.

1 – DIAL TONE detect ON. Unit hangs up after detecting 5-seconds of dial tone.

2 – SILENCE detect ON. Unit hands up after detecting 15-seconds of silence.

3 – BOTH ON.

2. Enter the hang-up option code _ (0, 1, 2 or 3) then press * (beep).

3. Press 0 # TOGETHER to end this programming step (beeeeeep).

NOTE: If the resident grants access, or denies access by pressing the # key, the unit will
hang up automatically. This hang-up sequence is only active if the resident denies
access and simply hangs up their telephone before pressing the # key.