Industrial Personal Computer Connections

92

1

Ground connection screw (protective earth screw for AC Industrial Personal Computer)

2

Supply voltage

3

Grounding strip

4

Switching cabinet

When grounding, follow the procedure below:

Step

Action

1

Check that the grounding resistance is 100

Ω or less.

2

When connecting the SG line to another device, ensure that the design of the
system/connection does not produce a ground loop.
NOTE: The SG ground connection screw are connected internally in the
Industrial Personal Computer.

3

Use 2.5 mm

2

(AWG 13) wire to make the ground connection. Create the

connection point as close to the Industrial Personal Computer as possible and
make the wire as short as possible.