Chapter 5 Installation and Wiring

5-9

‹ Connecting the FP Power Cord

(1)

Be sure that the FP’s power cord is not plugged in to the power supply.

(2)

Remove the Terminal Strip's clear plastic cover.

(3)

Remove the screws from the two (2) terminals (L,N) and FG (Frame Ground) Terminal, position the

Ring Terminals and reattach the screws. (Check each wire to make sure the connections are correct)

(4)

Reattach the Terminal Strip's clear plastic cover.

„FP3500-T41-24V/FP3600-T41-24V (Type DC)

‹ Power Cable specification

Use copper conductors only.

The torque required to tighten these screws are as follows:

Terminal Block: 0.5 to 0.6 N•m.

FG (Frame Ground) Terminal: 0.6 to 0.7 N•m.

Cable thickness

0.75 mm

2

to 2.5 mm

2

(18 AWG -12 AWG)

Core wire condition

Single or Stranded wire

Core wire length

• In case of using a strand wire, inappropriate twisting of the core wire may cause

short circuit between each wire, or between wire and the abutting electrode

contact.

DON’T

CONNECT

FG (Frame Ground) Terminal

7 mm [0.28 inch]