Proface FP3900 - 19 Flat Panel" User Manual

Page 134

Advertising
background image

Chapter 6 Setting up and Adjusting the FP unit

6-9

Enables/disables the Backlight burnout detect function.
(Default: ON)
When a burned-out backlight is detected, the Front LED flashes
alternately green and red, or a steady orange.
Touch-operation will be disabled when the backlight burns out,
which prevents the FP from sending input signals to the PLC.

Enables/disables the screen display Auto OFF function and sets the
time when the Auto OFF function is enabled.
(Default: OFF <Auto OFF function disabled>)

The Auto OFF function automatically turns off the display to
prevent the screen from burning out when the touch panel is not
used for some period of time. With this parameter, you can set the
time interval to turn off the screen display (how much time passes
before the screen display is turned off) when the touch panel is not
used. If the touch panel is not touched over the set time, the
backlight will automatically turns off.

Select the time period from 1 min, 3 min, 5 min, 10 min, and OFF
(Auto OFF function disabled).

When an input data resolution of 720 x 400 is used in the VGA text
mode, set this parameter to ON. For other resolutions, set this
parameter to OFF.
(Default: ON)

Enables/disables the click sound. With this parameter, the sound
level can also be adjusted.
(Default value: OFF <Click sound disabled>)

System Settings

Selection of the change item

Click Tone

720x400 Mode

Auto off Disp

BL Alarm

• Normally, the FP unit detects a backlight burnout by

monitoring the backlight’s current flow, however, the
FP may fail to detect this condition, depending on the
type of backlight problem.

Applies the setting and then returns to the top menu.

Cancels the setting and then returns to the top menu.

Adjustment button

Enables/disables to halt the data output procedure when two points
of the touch panel are pressed. (Default: OFF <Disable>)

Detect 2-Point Touch

• When doing the touch operation on a screen like the

desktop of Windows

®

, disable this function.

• Depending on the conditions, it may not be able to be

detected that the two points were pressed.

Set the touch panel ID number using the number 0 to 3, when
connecting to USB. (Default: 0)
Please use the default value normally.

USB Touch Panel ID

Enables/disables the buzzer sound in turning on the power.
(Default: ON < Buzzer sound enabled>)

Power on Buzzer