FP3000 Series User Manual

5-16

5.2.4

Precautions: Grounding

• Connect the FP’s FG terminal to an exclusive ground.

[diagram (a) - Grounding resistance of under 100

Ω.]

• If exclusive grounding is not possible, use a common

connection point. [diagram (b)]

• The grounding wire should have a cross sectional area

greater than 2mm

2

. Make the connection point as close

to the FP unit as possible, and make the wire as short as

possible. When using a long grounding wire, replace

the thin wire with a thicker wire placed in a duct.

• If this equipment does not function properly when

grounded, disconnect the ground wire from the FG ter-

minal.

5.2.5

Precautions: Input/Output Signal Lines

Input and output signal lines must be separated from operating circuit power cables.

If this is not possible, use a shielded cable and connect the shield to the FP chassis.

(a) Exclusive grounding (BEST)

(b) Common grounding (OK)

(c) Common grounding (BAD)

FP Unit

Other

Equipment

FP Unit

Other

Equipment

FP Unit

Other

Equipment