Removing a 2 x10-gigabit ethernet module, Installing a 2 x10-gigabit ethernet module, Replacing the fan tray – Brocade NetIron CER 2000 Series Hardware Guide (Supporting R05.6.00) User Manual

Page 91

Advertising
background image

Brocade NetIron CES 2000 Series and NetIron CER 2000 Series Hardware Installation Guide

81

53-1003029-02

Replacing the fan tray

6

CAUTION

For safety reasons, the ESD wrist strap should contain a series 1 Meg ohm resistor

Removing a 2 x10-Gigabit Ethernet module

Follow the procedure given below while removing a 2 x10-Gigabit Ethernet module.

1. Power off the Brocade device.

2. Use a #2 Phillips-head screwdriver to loosen the screws on the 2 x10-Gigabit module.

3. Remove the 2 x10-Gigabit module.

4. Place the 2 x10-Gigabit module in an anti-static bag for storage.

5. If you are removing the module without replacing it, install the blank faceplate in the front

panel.

Installing a 2 x10-Gigabit Ethernet Module

Follow these procedures when installing a 10-Gigabit Ethernet Module.

1. Power off the Brocade

device.

2. Use a #2 Phillips-head screwdriver to remove the blank faceplate or old module from the front

panel.

3. Install the 10-Gigabit module in the chassis.

4. Use a #2 Phillips-head screwdriver to fasten the screws on the 2 x10-Gigabit module. Affix the

screws loosely at first, then tighten them once you are sure the board is properly positioned.

Replacing the fan tray

The Brocade devices cooling fans use pull configuration to move the air from the front to the back
of the device.

The fans in the Brocade devices include six four-speed fans that operate at low speed, medium
speed, medium-high speed, and high speed based on the ambient temperature and configured or
default temperature thresholds. All fans operate simultaneously at the same speed. If a single fan
fails within the assembly, the fan tray should be replaced. The fan tray is hot swappable.

If a Brocade device remains operational during a fan tray replacement, the procedure must be
completed within 30 seconds.

NOTE

Fan trays are hot swappable. Hot swapping fan trays should be done within 30 seconds so the unit
will continue to function correctly without any fans. However, Brocade recommends that you
disconnect the power supply from AC or DC power before installing or removing the fan tray.