Rice Lake Condec UMC600IS User Manual
Page 23
Advertising
20
UMC 600IS Installation Manual
Figure 3-8. Analog Module Setup and Wiring
Table 3-11. Baud Rate and Switch SW1 Settings
Table 3-12. Description of Terminal Boards TB1 and TB2
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
S
S2
Baud rate
SW1 Setting
1
2
1200
Off
Off
2400
On
Off
4800
Off
On
9600
On
On
Mode
3
4
Normal operation
Off
Off
0 VDC/4 mA (test only)
On
Off
10 VDC/20 mA (test only)
Off
On
0–10 VDC/4–20 mA ramp (test only)
On
On
TB1
Description
TB2
Description
1
4–20 mA
1
Zero
2
Ground
2
Gross/Net
3
0–10 VDC output
3
Tare
4
Alarm
4
Start
5
5
Ground (–20 mA input) common
6
+20 mA TXD
6
RS-232 TXD
7
–20 mA TXD
7
+5 VDC
8
+20 mA RXD
8
–20 mA
9
-20 mA RXD
9
Demand print
NOTE: Jumper TB1-8 to TB2-7 (5 VDC) to make the analog output module an active device.