Installation and Wiring

5

2.2

Cable Requirements

Intrinsically safe cables used in the hazardous area are specified on the Control Drawings 54136, Sheets 2 and 3.

Since all cables have internal inductance and capacitance, only the cables listed are safe to use with this
intrinsically safe system. Table 2-2 provides specifications for maximum cable length based on group
classification. A list of Factory Mutual approved cables is shown in Table 2-3.

Figure 2-1. Intrinsically Safe System Diagram

Note:

Either power supply or battery can be used, but not both simultaneously.

Use only Factory Mutual approved cables.

Maximum Cable Length,

Group

Cable 1

Cables 2 & 3

A, B

75'

800'

C

300'

D

500'

E, F, G

Table 2-2. Maximum Cable Lengths

Factory Mutual Approved Cable

Cable

Type

Condec PN

Belden P/N

1

Power

45897 (

x

)

8618

2

Serial I/O

45898 (

x

)

9942

3

Load Cell

45898 (

x

)

9942

(

x

) = feet in increments of 50

Table 2-3. FM Approved Cable Lengths

Safe Area

Hazardous Area

Divisions I and 2
Class I, Groups A, B, C, D
Class II, Groups E, F, G
Class III

FM-Approved

load cells

(Up to 4)

Battery Power

Supply Models

Only

Junction

Box

Cable 3

Load Cell

Cable 2

Serial I/O

Power

Supply

Cable 1

Power

115 VAC

I/O

Isolation

Barrier

Battery

Charger

1

6

2

7

3

8

4

9

5

0

CE

ENT

TARE

RECALL

ZERO

NET

GROSS

TARE

lb/kg

CONV

PRINT

1 SET

POINT

2 SET

POINT

CAPACITY

600 x 0.1

ZERO

NET

GROSS

lb

kg

MOTION

!

Caution

Advertising