Supply

Control

Signal

4-20ma Setup 10 vdc Setup

1) S3-1 On, 3-2, 3, 4 Off (Default)

2) S1-2 On, S1-1, 3 Off (Default)

3) S2-1, 2, 3 On if 4-20ma

S2-1, 2, 3 All Off If 0-10vdc

4) Select Corresponding Control Signal

Type In Operation Setup Menu.

Main Stat/Sensor In

Modulating
High Limit Sensor

Outdoor
Temperature Sensor

Ground

S5079a,b,c

Figure 11-1

0-10 Vdc or 4-20mA Control Signal

Figure 11-2

RH Sensors/Transmitters

Supply

Main Stat/Sensor In

Modulating

High Limit Sensor

Outdoor

Temperature Sensor

Ground

Main Control

Sensor

High Limit

Sensor

Outside

Temperature Sensor

(Optional)

SYM Function Description

S1

and

S3

Power Supply

S1

S3

24VAC: S1-2 on S1-1, 3 Off S3-1 on S3-2, 3, 4 off
24Vdc: S1-1, 3 on S1-2 Off S3-2 on S3-1, 3, 4 off
10Vdc: S1-1, 3 on S1-2 Off S3-3 on S3-1, 2, 4 off
5Vdc: S1-1, 3 on S1-2 Off

S3-4 on S3-1, 2, 3 off

4 on 5 off: Thermistor
4 off and 5 on: Temp. Sensor

Switch Positions

3: Outside Temp. Sensor
On: Current Signal
Off: Voltage Signal
4&5: Outside Temp. Sensor

Input Signal Type Select

S2

For Sensors Select
(S1 and S3 together)

At one time, only one digit of S3-1, 2, 3 or 4 should be on.

2: High Limit Sensor

Settings

1: Stat/Main Sensor

Select RH sensor in sensor select window in operation setup menu

if using high limit sensor, select high limit sensor, set high limit set

point, 85% default.

If using out temperature sensor, select “outside temperature”.

Select signal type in operation setup menu.

Select desired RH in operation setup menu.

Verify PID settings in operation setup menu.

(For more information of PID Settings, see PID Section on

page 43.)

0-10 Vdc

4-20 mA