7. The device should be communicating, when using your BMS to modify points the Network Setup

has to be set to “Enable” before any other values can be changed. This can be found on the

variable list under “Network Enable”.

Controlling the Humidifier through Communication Port

If you are planning on sending a percent output via communication port follow these instructions. If

a controlling humidistat or the onboard controller on the humidifier with sensors are being used these

instructions do not apply to your application.

1. On the BMS system verify that the Network is “enabled” and that the Sensor Select is “humidi-

stat”.

2. Write the percent demand (0-100) to:

a. Modbus – data address 40002

b. BACnet – Analog Output

c. LonWorks - Data Array Name SINTA, Data Array Offset 2.

Changing ProtoCessor Configuration File

1. Run RUInet. Software can be found at www.protocessor.com.

2. Connect to the appropriate protocessor

3. Select “U,” Upload Configuration from FieldServer

4. The config.csv file will be saved in the root directory of the RUINET install. (It is a Comma

Separated Variables file, which can be opened with any spreadsheet or text editor).

5. Changing the file. Locate the Sysetm_Node_Id area in the Common Information section of the

file and change the value. The Node_ID value under the Server Side Nodes section will also

have to be updated. The Node_Name value can be changed to distinguish between the units

on the network. All of the default values can also be modified at this time. Changes can be

made to the baud rate of the MSTP connection in the config file as well, under the Server and

Client Side Connections section (This is only when using BACnet MSTP).

6. Save the file.

7. Using the “D” function in RUINET (Download Configuration to FieldServer) the config file can be

updated.

8. Return to the Main Menu and select “!” Restart FieldServer. When the ProtoCessor has been

re-started, it will have a new Node ID number and other changes implemented.

Obtaining xif File using RUInet

1. Run RUInet. Software can be found at www.protocessor.com.

2. In the main menu of RUInet, type ‘U’ for upload.

3. Type ‘O’ for other.

4. Type ‘R’ for remote.

5. Type ‘fserver.xif’ and hit the ‘Enter’ key.

6. Type ‘U’ to upload the file

7. If you are running RUInet through the ruinet.exe, the xif file will be saved in the same directory

as the RUInet executable.

8. If you are running RUINET through the Remote User Interface icon on the desktop, the xif file

will be saved in:

Start -> All Programs -> FieldServer Utilities -> Config File Folder