Resistance values of components – Armstrong World Industries 6100 User Manual

Page 42

Advertising
background image

42

Resistance Value of 6100/6300 Components

Component

Voltage

Resistance

Fill Valve

24Vac

18W

Drain Valve

24Vac

10W

Contractor

24Vac

7-9W

Thermocouple in Heating Elements -

0.51W

Heating Elements
208Vac and 380Vac 3kW

220Vac

46.0-48.6W

240Vac and 380Vac 3kW

240Vac

55-58W

480Vac and 380Vac 3kW

277Vac

72-78.2W

600Vac and 380Vac 3kW

346 Vac

112.4-122.4W

208Vac and 380Vac15/30kW

220Vac

9.2-10.7W

240Vac 15/30kW

240Vac

10.9-12.6W

480Vac 15/30kW

277Vac

14.5-16.8W

600Vac 15/30kW

346Vac

22.7-26.3W

208Vac and 380Vac9/18kW

220Vac

15.3-17.7W

240Vac 9/18kW

240Vac

18.2-21.1W

480Vac 9/18kW

277Vac

24.3-28.2W

600Vac 9/18kW

346Vac

37.9-43.9W

Power Transformer

120Vac

13.6W across H1-H2

15.1W across H3-H4

208Vac

22W across H1-H2

240Vac

29W across H1-H2

380Vac

77W across H1-H2

480Vac

125W across H1-H2

600Vac

194W across H1-H2

Power Transformer

(secondary)

All

Voltage

0.6W across X1-X2

0.4W across X1-X2

Resistance Value of 6500/6700 Components

Component

Voltage

Resistance

Fill Valve

24Vac

8.8W

Drain Valve

24Vac

4.1W

Thermocouple in Heating Elements

-

0.51W

Heating Elements
208, 240, 380V, 30/33, 5/40/45/50, 3/60kW 240Vac

7.4-9.1W

380V 48/72/96kW

220Vac

5.2-6.3W

480V 48/72/96kW

277Vac

8.1-10.0W

600V 48/72/96kW

346 Vac

12.8-15.7W

Power Transformer

Primary Loop

208Vac

18W across H1-H2

240Vac

21W across H1-H3

277Vac

24W across H1-H4

380Vac

40W across H1-H5

480Vac

22W across H1-H6

600Vac

22W across H1-H2

Secondary Loop

208Vac

1W across X1-X2

240Vac

1W across X1-X2

277Vac

1W across X1-X2

380Vac

1W across X1-X2

480Vac

1W across X1-X2

600Vac

1W across X1-X2

Note: All measurements should be made with the main power off

and the wires to the component being tested disconnected.

Resistance Values of Components

Advertising