Armstrong World Industries 6100 User Manual

Page 24

Advertising
background image

24

4. If fuses are OK, check voltage to contactor coil.

(a) If voltage is 24-28VAC at contactor coil, check coil resistance. It should be 8W with wires

disconnected. If resistance is OK, check voltage drops across the contactor.

(b) If no voltage to contactor coil, check continuity of wires from PC board to contactor. If

continuity is OK, PC board is likely defective.

5. Check voltage signal to power module. The voltage across TAB8-1 and TAB8-2 (low voltage signal

to power module) should be 12 Vdc.

(a) If no or low voltage, the PC board is likely defective.

(b) If voltage is OK, but green “SIGNAL” LED on the power module is not on, power module is

defective.

6. If green “LOAD” LED on power module is on, check voltage drops across power module.

Humidifier overfills with water on initial fill.

1. Check electrode canister (float canister for DI units) and level electrodes for debris or scale build

up. Clean as needed. See Page 21 for cleaning procedure for electrodes. On DI Units, the high

water float switch may be defective or “hung up”. Check continuity across wires to the switch.

Make sure switch movement is vertical so float lever arm swings freely.

2. The fill valve may be stuck open. Turn off power to the humidifier. If fill valve does not close,

clean or replace valve.

3. If the high water circuit is closed and the fill valve shuts off when the power is turned off, the PC

board is defective.

Humidifier runs continuously, %RH is well over set-point.

1. Verify humidistat signal isn’t sending false 100% demand.

2. Verify humidistat or RH sensor is wired correctly and stat/sensor dip switches (S2 & S3, See

Fig. 10-1 and 11-1) on the PC board are set correctly for the humidistat signal.

3. If humidifier generates steam with the humidistat disconnected.

(a) Check for power at the contactor coil. If 24-28 VAC, PC board is defective.

(b) Check voltage drop across contactor. If voltage drop is low (it should be line voltage),

remove, disassemble and inspect contactor.

(c) Check green “SIGNAL” LED on power module. If it is ON or blinking, PC board is likely

defective.

(d) Check voltage drop across power module. If voltage drop is low (it should be line voltage),

power module triacs may be failed closed. Shut off main power and perform continuity check

across high voltage input and output terminals. Continuity indicates a shorted triac. Note:

Some power modules have two triacs rather than three. Check schematic on power module

to

verify.

(e) Check to see if the aquastat is reading a valve lower than the aquastat temp setting.