Installation

HC-6100/6300 Mounting

The HumidiClean models HC-6100/6300 are designed to be wall mounted. A wall mounting bracket

and lag screws are provided for mounting on 410 mm (16”) centers. The operating weight of the unit

is 106 kg (233 lbs). A clearance of 600 mm (23”) on the front and sides of the cabinet is required for

servicing.

1. Position wall mounting bracket level on wall and mark hole pattern. Make sure holes line up with

studs or other sturdy structure.

2. Use 3/8” x 1-1/2” lag screws provided to secure the bracket.

3. Hang the humidifier on the wall mounting bracket. The dry weight of the unit is 70 kg (154 lbs).

HC-6500/6700 Mounting

The HC-6500/6700 HumidiClean is designed to be floor mounted on a level surface. The operating

weight is 230 kg (507 lbs), a clearance of 610 mm (24”) is required for the front and sides.

Water Fill Supply

The humidifier can use any potable or purified water supply. Water pressure must be 25-120 psig.

Water temperature must be less than 60°C (140°F). The fill rate is .31 GPM for HC6100/6300 and 1.2

GPM for HC6500/6700 units.

1. Install a shut-off valve near the unit.

2. Connect the water supply to the 3/8” compression fitting on the fill water solenoid valve on models

HC-6100/6300. The HC6500/6700 is supplied with a compression fitting for 10mm plastic tubing. A

6’ piece of 10mm plastic tubing is included for the larger models. The access for the water

supply tubing is under the fill valve in the bottom wall.

Electrical Service Wiring

1. Connect main power supply wiring to high voltage terminals in unit. Read breaker size required on

humidifier’s nameplate and refer to Table 7-1 and 7-2 for HC-6100/6300 wire (gage) required;

Table 7-1, 7-3 and 7-4 for HC-6500/6700. Make sure an interlocking circuit breaker or safety

switch (not furnished) is accessible and within sight of the unit.

2. The humidifier cabinet must be grounded. A ground lug is provided in the cabinet.

3. Use only wire with copper conductors rated at 90°C (194°F) or higher for power supply and

grounding.