49

be extracted from the protocessor using RUInet.

(see Obtaining .xif File using RUInet)

7. A few minutes after the unit is powered on the

Initialization LED should light. The protocessor will

not communicate until this LED is illuminated.

8. When the Lon device is commissioned the Lon LED

on the protocessor will stop blinking and will be on

solid.

9. The device should be communicating, when using

your BMS to modify points the Network Setup has

to be set to “Enable” before any other values can

be changed. This can be found on the variable list

under “Network Enable”.

10. After any permanent changes are made to the

variables on the BMS side these should be saved

at the unit as well to set them as defaults. This can be done by going in to the Operation Setup

menu in the “Save Settings” screen.

BACnet Protocol Setup

1. Attach protocessor into upper right hand corner of

main pc board.

a. BACnet MSTP - The ethernet connection

should be going to the inside of the board.

b. BACnet IP - The ethernet connection goes to

the outside of the board.

Make sure that all pins are seated properly and

making a good connection. (See Figures 49-2 and

49-3.)

2. Connection

a. BACnet MSTP - Connect three-wire BMS

system to RS485 terminal on protocessor.

b. BACnet IP – Connect to ethernet port.

3. Make sure that all proper connections are made and that

the installation instructions that start on page 6 have been

adhered to. Power unit on.

4. With the humidifier powered on connect to the

protocessor via the ethernet port through RUInet (see

Changing ProtoCessor Configuration File). Typically this

is needed if the default values need to be changed or if

there is more than one unit operating in the system on

the same protocol that would require a Node ID change.

Note that any time the system loses power the unit will

divert back to the default settings.

5. When the humidifier is powered access the Operation

Setup menu through the front display and set the

following information:

a. Communication Type – PSP

b. Secondary ID - 1

6. Now the changes to the actual unit are complete use Table 53-1 BACnet Variants List to help

set up the required points in the Building Management System.

Figure 49-2. BACnet MSTP Wiring

Figure 49-3. BACnet IP Wiring

Figure 49-1.