Armstrong World Industries 6100 User Manual
Page 15
15
Operation Setup - Continued
Drain Frequency
6
Default: 12 hours
12 (Default)
24
48
96
Real
Time
Time
Settings
24
Hour
Clock
Drain Time
1
5
(Default)
10
Load Default
Reset all to Default?
Confirm Cancel
Signal Type
0-10
Vdc
(Default)
0-5VDC
1.9V
-
3.9V
4-20mA
Sensor Select
Humidistat
(Default)
RH
Sensor
High
Limit
Sensor
High
Limit
Set
Point
1%
-
99%
(85%
Default)
Outside
Temperature
High Limit Set 1°C / Low Limit Set 1°C
Lowest
RH
Set
Point
15%
(Default)
PID Settings
PB Proportion Brand 0-500
PID PB 15; PID IRV 125
IRV Integral Reset Value 0-500
PIDF DG 0; PID SI 10
DG Derivative Gain 0-500
SI
Interval
0-500
Failure Record
Failure List
01 05-04-01 16:00 (example)
See Page 25 for list of all possible errors.
Fill time out to low level
Display the RH graph
RH graph of the last 30 days
This menu can be shown when RH sensor is selected.
Set Date and Time
YYY_MM-DD; Time (24 Hr. Format)
Date and Time from realtime IC
Save Settings
Save User’s Settings
Confirm
Cancel
Must be done after any ‘Operation Setup’ menu changes.