g. When operation has finished, close the “SAM-BA” window first, and then click the icon “remove

the USB hardware” to disconnect the link between computer and board. After reminder by

system, disconnect the power supply from breaker and pull out the USB cable.

h. The soft refresh of HC-6000 is complete, restart the unit.

Introduction to Communications

Modbus Protocol Setup

1. Wire to the RS-485 port, following Figure 48-1.

2. Make sure that all proper connections are made and that

the installation instructions that start on page 6 have been

adhered to. Power unit on.

3. Once unit is on go to “Operation Setup” and verify the

following data:

a. Network Setup – Enabled

b. Secondary ID – Default is Secondary ID 1, but set to fit

your system

(If using multiple units, each unit should have a different

Secondary ID)

c. Communication Type – Modbus

(When the screen shows Modbus hit enter to go to

advanced settings)

i. Baudrate – Default is 9600, but set to match

your system

ii. Parity – Default is Even Parity, but set to match your system

iii. Stop Bit – Default is 1 Bit(s), but set to match your system

4. Now the changes to the actual unit are complete use Table 51-1 Modbus Variants List to help

set up the required points in the Building Management System.

LonWorks Protocol Setup

1. Attach protocessor into upper right hand corner of main pc board. The ethernet connection

should be going to the inside of the board. (See Figure 49-1) Make sure that all pins are seated

properly and making a good connection.

2. Land two-wire BMS system to wire terminal on protocessor. (See Figure 49-1)

3. Make sure that all proper connections are made and that the installation instructions that start

on page 6 have been adhered to. Power unit on.

4. With the humidifier powered on connect to the protocessor via the ethernet port through RUInet

(see Changing ProtoCessor Configuration File). Typically this is needed if the default values

need to be changed or if there is more than one unit operating in the system on the same pro-

tocol that would require a Node ID change. Note that any time the system loses power the unit

will divert back to the default settings.

5. When the humidifier is powered access the Operation Setup menu through the front display

and set the following information:

a. Communication Type – PSP

b. Secondary ID - 1

6. Now the changes to the actual unit are complete use Table 52-1 LonWorks Variants List to help

set up the required points in the Building Management System. The .xif file is available and can

Figure 48-1. Modbus RS485 Wiring