Drainage – Armstrong World Industries 6100 User Manual
Page 7
7
Air Gap
Figure 7-1 HC-6100/6300/6500/6700
Table 7-1. Recommended Branch Circuits
Rating Amp
1-12
13-15
16-20
21-24
25-32
33-40
41-48
49-64
68-80
81-100
101-120
121-140
141-60
Wire
(AWG)
14
12
10
10
8
8
6
4
3
1
0
0
0
(mm2)
3
4
6
6
10
10
16
25
35
50
50
70
95
Circuit Breaker
15
20
25
30
40
50
60
80
100
125
150
175
200
Table 7-2. Steam Capacities and Rating Amperages
Volts
(Vac)
HC6100/HC6100DI
HC6300/HC6300DI
3 KW Unit
9 KW Unit
15 KW Unit
18 KW Unit
30 KW Unit
Nominal
Amperage
Rating
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage Rating
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Steam
Output
kg/hr
(lb/hr)
Phase
Phase
Three
Phase
Three
Phase
Three
Phase
Single
Three
Single
Three
208
13.3
7.7
3.8 (8.3)
39
23
11 (24)
37
18 (40)
46
22 (48)
74
36 (80)
240
12.9
7.5
4.1 (9)
38
22
12 (27)
36
20 (45)
44
25 (54)
72
41 (90)
200
-
4.7
-
14
23
28
46
480
-
3.8
-
11
18
22
36
600
-
3
-
9
15
18
30
Table 7-3. Steam Capacities and Rating Amperages
Volts
(Vac)
HC6500/6500DI
30 KW Unit
33.5 KW Unit
40 KW Unit
48 KW Unit
45 KW Unit
Nominal
Amperage
Rating Three
Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
208
84
41 (90)
-
-
-
-
-
-
125
61 (135)
240
-
-
-
-
96
54 (120)
-
-
-
-
400
-
-
51
45 (100)
-
-
73
65 (144)
-
-
480
-
-
-
-
-
58
-
-
600
-
-
-
-
-
47
-
-
Table 7-4. Steam Capacities and Rating Amperages
Volts
(Vac)
HC6500/6500DI
HC6700/HC6700DI
50.3 KW Unit
60 KW Unit
72 KW Unit
96 KW Unit
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating Three
Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
Nominal
Amperage
Rating
Three Phase
Steam
Output
kg/hr
(lb/hr)
240/220
-
-
144
82 (180)
-
-
-
-
400/380
77
30 (68)
-
-
110
98 (216)
145
130 (288)
480
-
-
-
-
87
116
600
-
-
-
-
70
93
Drainage
Connect HC-6000 drain to suitable waste drainage
system. HC-6000 drain water may be as hot as 70°C
(158°F). Use clear drain hose provided and 25 mm (1”)
copper pipe pitched away from unit at 25 mm (1”)
inch per foot. An air gap to prevent back flow is required.
See Figure 7-1.