Table 52-1. bacnet variable list – Armstrong World Industries 6100 User Manual

Page 52

Advertising
background image

52

Table 52-1. BACnet Variable List

BACnet data type

address

description

Value / (unit)

attribute

1

Fill valve status

0:off 1:on

2

Drain valve status

0:off 1:on

3

contactor 1 status

0:off 1:on

4

contactor 2 status

0:off 1:on

5

contactor 3 status

0:off 1:on

6

contactor 4 status

0:off 1:on

8

Network control

0:Local 1:Remote

1

comm type

0:485 1:PSP

2

Sensor select

0:Humidistat 1:RH sensor

3

High limit sensor select

0:not use 1:use

4

Outside temperature

0:not use 1:use

5

Network enable

0:disable 1:enable

6

Modulating Fill enable

0:enable 1:disable

1

Desired RH / Demand

(%)

2

Steam Output

(kg/hr)

3

Water level

0:low 1:normal 2:high 3:exception

4

Run status

0:Idle 1:Steam gen. 2:Cycle drain 3:End of season drain 4:Bed dring 5:Failure 6:Drain 7:heat 8:Manual drain
9:Fill 10: Test 11: Manual stop 12: Empty drain

5

Bed life

(hours)

6

Bed life

(Minutes)

7

Run Time

(hours)

8

Run Time

(Minutes)

9

Drain Freq

(hours)

10

Drain Freq

(Minutes)

11

Idle Time

(hours)

12

Idle Time

(Minutes)

13

RH / Demand (Analog input)

(%)

14

Duct value

(%)

15

Outside temperature

(

℃)

16

Water temperature

(

℃)

17

Heat temperature

(

℃)

18

Failure

1:Over temperature 2:High humidity/sail switch circuit is open 3:Illegal level switch state 4:Unit have reached
100% of bed life 5:Fill time out to low level 6:Water level dropped below level during normal run 7:Fill time
out from low to high level

19

Contactor number

1,2,3,4

20

Heating Element Power

0:1000W 1:3000 2:5000W 3:6650W 4:8000W

1

Language Select

0:English 1:Chinese

2

Set RH / Demand

(%)

3

Duct High Limit set point

(%)

4

Outside temp. high set point

(

℃)

5

Outside temp. low set point

(

℃)

6

Outside RH low set point

(%)

7

Run mode

0:Steam Gen 1:Manual Drain 2:Manual Fill 3:Unit stop

8

AQUASTAT

(

℃)

9

Bed Life

0:500hours 1:750hours 2:1000hours 3:1250hours 4:1500hours 5:1750hours 6:2000hours 7:2250hours
8:2500hours 9:3000hours 10:No bed

10

Drain Cycle

0:6hours 1:12hours 2:24hours 3:48hours 4:96hours 5:Real time drain

11

Drain duration

0:1Minutes 1:5Minutes 2:10Minutes

12

Signal type

0:0-10V 1:0-5V 2:1.9-3.9V 3:4-20mA

13

PID_DIV

14

PID_PB

15

PID_SI

(second)

16

PID_DG

17

Modulating Fill Cycle

(second)

18

Modulating Fill duration

(second)

19

Water temp. compensate

(

℃)

20

Themocouple compensate

(

℃)

analog ouput

BACNet variants list

binary input

binary output

Analog input

read only

read / write

read only

read / write