Remote Controlled

The analog outputs on the XTDL-HT™ can be remotely controlled via its Modbus interfaces. In addition
to configuring the channels remotely, the instrument allows the Modbus master to directly control its
analog outputs. This allows the DCS system to control another device via the XTDL-HT™ without setting
up a Remote Terminal Unit.

Remotely change the analog output signal

Set Modbus register Analog Output Variable to 32768
Set Modbus register Analog Output Value to the
desired digital-to-analog converter input value

Channel 1

Channel 2

Analog Output Variable

Register 40405

Register 40415

Analog Output Value

Register 40410

Register 40420