COSA Xentaur Xentaur XDTL-HT User Manual

Page 53

Advertising
background image

53

Appendix B: Modbus Registers

Register
Number

Address

Access

Level

Data
Type

Description

Values

40914

913 (391h)

Admin

16-bit

PID 2 integral time

Valid values are 0 - 65535

40915

914 (392h)

Admin

16-bit

PID 2 derivative time

Valid values are 0 - 65535

40917

916 (394h)

Admin

16-bit

PID 3 variable

See PID 1 variable

40918

917 (395h)

Admin

Float

PID 3 setpoint

Valid values are -100 - 99999.9

40920

919 (397h)

Admin

Float

PID 3 proportional gain

Valid values are -99999.9 - 99999.9

40922

921 (399h)

Admin

16-bit

PID 3 integral time

Valid values are 0 - 65535

40923

922 (39Ah)

Admin

16-bit

PID 3 derivative time

Valid values are 0 - 65535

40925

924 (39Ch)

Admin

16-bit

PID 4 variable

See PID 1 variable

40926

925 (39Dh)

Admin

Float

PID 4 setpoint

Valid values are -100 - 99999.9

40928

927 (39Fh)

Admin

Float

PID 4 proportional gain

Valid values are -99999.9 - 99999.9

40930

929 (3A1h)

Admin

16-bit

PID 4 integral time

Valid values are 0 - 65535

40931

930 (3A2h)

Admin

16-bit

PID 4 derivative time

Valid values are 0 - 65535

System Registers

41001

1000 (3E8h)

User

16-bit

System year

Valid values are 0 - 65535

41002

1001 (3E9h)

User

16-bit

System month

Valid values are 1 - 12

41003

1002 (3EAh)

User

16-bit

System day

Valid values are 1 - 31

41004

1003 (3EBh)

User

16-bit

System hour

Valid values are 0 - 23

41005

1004 (3ECh)

User

16-bit

System minute

Valid values are 0 - 59

41006

1005 (3EDh)

User

16-bit

System second

Valid values are 0 - 59

41007

1006 (3EEh)

User

16-bit

Daylight saving enable

0=Disabled
1=Enabled

41008

1007 (3EFh)

User

16-bit

Date format

0=mm/dd/yyyy
1=dd/mm/yyyy

41010

1009 (3F1h)

User

16-bit

32-bit word order

0=Low word first
1=High word first

41011

1010 (3F2h) Read-Only

16-bit

Model number

41012

1011 (3F3h) Read-Only

32-bit

Serial number