16 5.0 programming, Caution – Edwards Signaling 2400 Series User Manual

Page 24

Advertising
background image

16

5.0 PROGRAMMING

Panel Configuration Worksheets may be found at the end of this manual. These worksheets should be
filled out prior to programming the panel, and saved with this manual should further programming be
required at a later date. Refer to the PANEL PROGRAMMING drawing during the programming process.
The reverse side of the base panel identification labels are programming templates. Remove, reverse, and
re-insert the template labels as a programming aid. Dialer programming is covered in section 5.6.

CAUTION

The panel MUST be reprogrammed whenever permanently adding (or removing) option

modules to (from) the system. Replacing a module with another module of the same type does

NOT require reprogramming.

DO NOT DISCONNECT AC POWER WHILE IN THE PROGRAMMING MODE!

The panel is shipped from the factory with the default configuration denoted by

in Table 5.1. The panel

defaults may be re-programmed any time during the programming sequence by simultaneously pressing
the

TROUBLE SILENCE

and

RESET

switches for one second, which also returns you to the start of the

programming process. The programming step (of the panel being programmed) is indicated by the flash
phase of the green Power LED. The program variable and flash phase is indicated in Table 5.2.

Table 5.1 - Programmable Features

= Default

Initiating Device Circuit (IDC)

1

Non-Verified Alarm

2 Verified High Impedance Detector w/Contact Device (See Note)
3 Verified Low Impedance Detector Only
4 Supervisory
5 Waterflow & Supervisory
6 Waterflow w/retard & Supervisory

Indicating Appliance Circuit (IAC)

1

Affected by Alarm Silence Features

2 Not affected by Alarm Silence Features

IAC Signal Rates

1

Continuous

2 March Time @ 120 SPM
3 Temporal 3-3-3
4 Continuous ON for 10 Seconds., 5 Seconds. OFF
5 March Time ON for 10 Seconds., 5 Seconds. OFF

Alarm Silence Inhibit Timer

1

No Timer

2 One Minute Inhibit
3 Two Minute Inhibit
4 Three Minute Inhibit

Automatic Signal Silence Timer

1

No Timer

2 10 Minutes to Silence
3 20 Minutes to Silence
4 30 Minutes to Silence

Auxiliary Power Reset

1

Auxiliary Power NOT Reset

2 Auxiliary Power Reset

NOTE: Do Not use this option. High Impedance detectors are not presently available.

Advertising