Table 10.11 - ULC Device & Panel Compatibility - Initiating Devices

Cat. #

Description

UL

Identifier

Max. # Devices

per IDC Zone

Options

291C

135ºF (57ºC) Heat Detector

001

50

1

292C

197ºF (92ºC) Heat Detector

001

50

1

293C

135ºF (57ºC) Heat Detector

001

50

1

294C

197ºF (92ºC) Heat Detector

001

50

1

5956A

Fire Alarm Indicator - LED

NA

NA

6249C

Ionization Smoke Detector c/w Base

001

50

3,5

6250C

Ionization Smoke Detector

001

50

1,5

6260A-100

Duct Detector/Sensor Housing (housing only)

NA

NA

6260C-005

Duct Detector Assembly, Low Velocity

NA

NA

6262A-001

Fire Alarm Indicator/Test Station

NA

NA

6264C-001

Ionization Detector, Duct

001

50

1,2,5

6264C-005

Ionization Detector, Duct, Low Velocity

001

50

1,2,5

6266C-001

Photoelectric Detector, Duct

001

30

1,2,5

6269C

Photoelectric Smoke Detector c/w Base

001

30

3,5

6269C-003

Photoelectric/Heat Detector c/w Base

001

30

3,5

6270C

Photoelectric Smoke Detector

001

30

1,5

6270C-003

Photoelectric/Heat Detector

001

30

1,5

6426A

Beam Smoke Detector - 4-wire

NA

NA

4

NOTES

1.

These detectors plug into the following base: Cat.# 6251B-001A. Compatibility ID for all bases is 001.
The Cat.# 5956A remote LED may also be used with these bases.

2.

These detectors are used with the following detector housings: Cat.# 6260A-100 and Cat.#6260C-005
duct detector assembly and fire alarm indicator/test station.

3.

The Cat.# 5956A remote LED may also be used with these bases.

4.

The Cat.# 6424A Beam Smoke Detector is powered from auxiliary power.

5.

Low impedance detectors. (Refer to Programming Section for proper operation.)

6.

High impedance detectors. (Refer to Programming Section for proper operation.)