Edwards Signaling 2400 Series User Manual

Page 46

Advertising
background image

38

Table 10.2 - 60 Hours Supervisory, 5 Minutes of Alarm

Signal Circuit Alarm Current for 5 Minutes

Aux. Circuit Current: 0-0.5 Amps for 5 Minutes

Panel Current Load

Signal Circuit Alarm Current (A)

Aux. Sup

Current

#

Zones

#

Option

Modules

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

0 mA

Amp/Hour Battery Size

2

0

4.5

4.5

4.5

4.5

4.5

6.5

6.5

6.5

2

1

6.5

6.5

6.5

6.5

6.5

6.5

6.5

6.5

2

2

6.5

6.5

6.5

8.0*

8.0*

8.0*

8.0*

8.0*

2

3

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

4

0

6.5

6.5

6.5

6.5

6.5

6.5

6.5

6.5

4

1

6.5

6.5

6.5

8.0*

8.0*

8.0*

8.0*

8.0*

4

2

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

8

0

8.0

8.0

8.0

8.0

8.0

8.0

8.0

8.0

25 mA

Amp/Hour Battery Size

2

0

6.5

6.5

6.5

6.5

6.5

6.5

6.5

6.5

2

1

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

2

2

8.0*

-

-

-

-

-

-

-

4

0

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

4

1

8.0*

-

-

-

-

-

-

-

50 mA

Amp/Hour Battery Size

2

0

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

8.0*

-

* = Must Purchase Auxiliary Battery Box P/N 2400-BATBOX Separately.