10.0 APPENDICES

10.1 Appendix 1 - Battery Calculations

10.1.1 Battery Tables
Maximum battery size is 8.0 AH. Maximum battery size with optional 2400-BATBOX(R) Battery Cabinet is
10 AH. Refer to Replacement Parts Section for part numbers.

The battery tables allow quick battery selection. Three battery tables are provided for the three most
common Supervisory and Alarm Time combinations.

For instructions on using the battery tables, refer to the section entitled Using the Battery Tables.

Table 10.1 - 24 Hours Supervisory, 5 Minutes of Alarm

Signal Circuit Current: 4 Amps for 5 Minutes

Aux. Circuit Current: 0-0.5 Amps for 5 Minutes

Panel Current Load

Aux. Power Supervisory Current (A)

0

25

50

75

100

125

150

#

Zones

#

Option

odules

Amp/Hour Battery Size

2

0

4.5

4.5

4.5

4.5

6.5

6.5

6.5

2

1

4.5

4.5

4.5

6.5

6.5

6.5

8.0*

2

2

4.5

4.5

4.5

6.5

6.5

6.5

8.0*

2

3

4.5

4.5

6.5

6.5

6.5

8.0

8.0*

4

0

4.5

4.5

4.5

6.5

6.5

6.5

8.0*

4

1

4.5

4.5

4.5

6.5

6.5

6.5

8.0*

4

2

4.5

4.5

6.5

6.5

6.5

8.0*

8.0*

8

0

4.5

4.5

6.5

6.5

6.5

8.0

8.0*

8

1

4.5

6.5

6.5

6.5

8.0

8.0

-

8

2

4.5

6.5

6.5

6.5

8.0

8.0

-

8

3

4.5

6.5

6.5

8.0

8.0

8.0

-

* = Must Purchase Auxiliary Battery Box P/N 2400-BATBOX Separately.