Edwards Signaling 2400 Series User Manual

Page 42

Advertising
background image

34

Table 9.1 - Specifications

Base Panel Assemblies

Environment
Relative Humidity
Operating Temperature

85% @ 86°F (30°C)
32°F to 120°F (0°C to 49°C)

Table 9.2 - Specifications

2400-BPA Base Panel Class A (Style D/Z) Converter Module (P/N 46199-1072)

Expansion Space

None

IDC Wiring

Converts two Style B Circuits into two Style D Circuits

IAC Wiring

Converts two Style Y Circuits into two Style Z Circuits

Weight

0.4 lbs (0.18 Kg)

Table 9.3 - Specifications

2400-2IDC IDC Module (P/N 240457)

Expansion Space

1

IDC Zones

Two Style B, verification optional

Detector Capacity per IDC Circuit

30 - Photoelectric Smoke
50 - Ionization Smoke
Detector voltage 17.85 to 26.4 VDC.
Max. Ripple = 400 mVDC.
Max. Alarm Current = 33 mADC
Refer to Compatibility Section.
Relay Bases are NOT supported.

IDC EOL

4.7K

, 1/2 Watt

Max. Circuit Resistance

50

Indicators and Controls

Trouble LED
Enable/Disable Switch

Weight

0.3 lbs (0.14 Kg)

Table 9.4 - Specifications

2400-IDCA IDC Class A (Style D) Converter Module (P/N 46199-1074)

Expansion Space

None

IDC Wiring

Two Class A (Style D) Circuits

Weight

0.3 lbs (0.14 Kg)

Table 9.5 - Specifications

2400-RCT Relay/City-Tie Module (P/N 240459)

Expansion Space

1

Configurable Operation

Reset, Alarm, Trouble, or Supervisory

Master Box Operation
Max. Wiring Resistance
Trip Current

Nominal 24 VDC
25

200 mA into 14.5

coil

Reverse Polarity Operation
Loop and Receiver Resistance
Current Range

Nominal 24 VDC
1.5 K

, Max.

2.5 to 9.9 mA

Dry Contact (Shunt)

Normally-Open OR Normally-Closed, 24 VDC @ 1 A
See Application Section for proper installation.

Indicators and Controls

Trouble LED
Enable/Disable Switch

Weight

0.4 lbs (0.18 Kg)