33 9.0 specifications – Edwards Signaling 2400 Series User Manual

Page 41

Advertising
background image

33

9.0 SPECIFICATIONS

Table 9.1 - Specifications

Base Panel Assemblies

Dimensions (HWD)
2412 & 2414 Panels
Back box
Finished
2418 Panel
Back box
Finished

12" x 14" x 2.75" [30.5 cm x 35.6 cm x 7.0 cm]
14" x 15.75" x 1.125" [35.6 cm x 40.0 cm x 2.9 cm]

13" x 20.19" x 2.75" [33.0 cm x 51.3 cm x 7.0 cm]
15" x 22" x 1.125" [38.1 cm x 55.9 cm x 2.9 cm]

Weight (less battery)
2412 Panel
2414 Panel
2418 Panel

12 lbs. (5.5 Kg)
12.5 lbs. (5.7 Kg)
16 lbs. (7.3 Kg)

Input Power

120 VAC @ 3.5 A, 50 - 60 Hz

Output Power - Signals

24 VDC @ 4A. Refer to Compatibility Section.

Auxiliary Power

Maximum Capacitance

24 VDC nominal @ 500 mA., filtered, reset
programmable. Refer to Compatibility Section.
100

m

F

Option Module Spaces

2412 Panel: 3 Input/Output
2414 Panel: 2 Input/Output
2418 Panel: 3 Output

Battery Type
2412 & 2414 Panels

2418 Panel

2400-BATBOX(R) Battery Cabinet

2 x 12 V, 6.5 AH, Lead-Acid

2 x 12 V, 6.5 AH, Lead-Acid
4 x 6 V, 8.0 AH, Lead-Acid
2 x 12V, 10 AH Lead-Acid

Ground Fault Detection

10K

to earth, all field wiring except AC input and

common relay contacts

IDC Zones
Style
Configurations

Two Class B (Style B) or Class A (Style D)
Verified or non-verified alarm
Waterflow or waterflow with retard
Supervisory

Detector Capacity per IDC Circuit

30 - photoelectric smoke
50 - ionization smoke
Detector voltage 17.85 to 26.4 VDC.
Max. Ripple = 400 mVDC
Max. Alarm Current = 33 mADC.
Refer to Compatibility Section.
2-Wire Relay Bases are NOT supported.

Supervisory Series & EOL Resistors
(P/N 46071-0409 for ULI)
(2 each P/N EOL-P1 for ULC)

1.1K

, 1 Watt; 3.6K

, 1/2 Watt

IDC End-Of-Line Resistor

4.7K

, 1/2 Watt

Max. IDC Circuit Field Wiring Resistance

50

IAC Circuits

Two Class B (Style Y), optional Class A (Style Z)

IAC Output Power/Ckt

Nominal 24 VDC @ 2.5A; 4.0 Amp total for both zones

IAC EOL

4.7K

, 1/2 Watt

System Alarm Relay

Form C, 24 VDC @1 A. Refer to Compatibility Section for
proper installation.

System Trouble Relay

Form C, 24 VDC @1 A. Refer to Compatibility Section
for proper installation.

Indicators

Power, System Trouble, Zone Disabled, Alarm Silenced,
Alarm, Signal circuit trouble (2), and Ground Fault LEDs

Controls

Trouble Silence, Alarm Silence, Reset, and Zone
Enable/Disable Switches

Max. Battery Charger Current

500 mADC