Door holders – Edwards Signaling 2400 Series User Manual

Page 75

Advertising
background image

0

0

24

24

115

115

230

230

NC

NC

NC

C

C

C

NO

NO

NO

ON

ON

MR-101 (MR-104)

SPDT CONTACTS

10 AMPS @

115 VAC

MR-201 (MR-204)

DPDT CONTACTS

10 AMPS @ 115 VAC

AUX

AUX

AUX

ALARM

ALARM

ALARM

TROUBLE

TROUBLE

TROUBLE

SIG1

SIG1

SIG2

SIG2

INP1

INP1

INP2

INP2

PGM
MODE

PGM
MODE

+

+

+

+

+

+

+

+

+

+

+

CONTROL PANEL

CONTROL PANEL

CONTROL PANEL

CITY TIE/RELAY MODULE

CAT.# 2400-RCT

REFER TO

RELAY/CITY-TIE

DRAWING SHEET

FOR JUMPER

CONFIGURATION

OR

+

+

+

NOTES

NOTES

1. FAILSAFE WIRING SHOWN. ANCILLARY RELAYS ARE NORMALLY
ENERGIZED AND WILL DE-ENERGIZE ON ALARM.

1. CONTACTS SHOWN IN NORMAL
CONDITION.

2. USE OF RELAY/CITY-TIE MODULE PROVIDES ENABLE/DISABLE
CAPABILITY FOR ANCILLARY RELAYS.

3. STANDBY BATTERY CALCULATION REQUIRED. SEE APPENDIX FOR
SPECIFIC INFORMATION.

8. REFER TO APPENDIX FOR COMPATIBLE DEVICES.

9. USE ONLY DOCUMENTED APPLICATIONS.

4

6

7

10

10

4

CONTACT RATING 24 VDC @ 1 AMP.

AUXILIARY POWER 24 VDC @ 500 mA.

POWER LIMITED WIRING.

NON-POWER LIMITED WIRING.

WIRING IS SUPERVISED FOR SHORTS AND GROUND FAULTS.

JUMPERS

1, 2, AND 8
INSTALLED

EDWARDS ULI LISTED

1500 SERIES

DOOR HOLDERS

24 VAC @ .11 AMPS

(9 DEVICES MAX.)

120 VAC

UTILITY

LISTED

FIRE PROTECTIVE

SIGNALING TRANSFORMER

120/24V, 50/60 HZ., 40 VA

DOOR HOLDERS

2. WIRING RUNS ARE NOT
SUPERVISED.

[ELOZRLY2.CDR]
03/08/95

ENABLE/DISABLE

SWITCH

5

5

5

7

6

6

7

+

NC/O

C

TB2

TB1

1

1

2

2

3

3

4

5 6 7 8

JP1

JP2

U10

S1