6.0 OPERATION

Table 6.1 - Panel Indicators

Indicator

Function

Zone Disabled LED

YY

PAUSE

YY

PAUSE

YY

... - One or more zones disabled

YYY

PAUSE

YYY

PAUSE

YYY

... - Audible test mode

YYYY

PAUSE

YYYY

PAUSE

YYYY

... - Silent test mode

Power LED

ON - AC power normal
OFF - AC power fail

Zone Alarm (Red) LED

STEADY - Zone in alarm

Zone Trouble (Amber) LED

STEADY - Supervisory condition restored
RAPID FLASHING - Zone in supervisory alarm.
SLOW FLASHING - Zone in trouble condition.

YY

PAUSE

YY

PAUSE

YY

... - Zone disabled

Alarm Silenced LED

ON - The audible alarm signals have been silenced

Alarm LED

ON - System in the alarm state

System Trouble LED

SLOW FLASHING - System in Trouble state
RAPID FLASHING - System in Supervisory state
STEADY - Trouble buzzer silenced

Signal Trouble, Ckt #1 LED

SLOW FLASHING - Open/short on IAC #1 wiring

Signal Trouble, Ckt #2 LED

SLOW FLASHING - Open/short on IAC #2 wiring

Ground Fault LED

SLOW FLASHING - A ground fault condition exists on the panel or field wiring

Normal Mode
In the Normal Mode, the panel is operating properly and has not detected any Alarm, Supervisory, or
Trouble conditions. The green power LED is ON and all other LEDs are OFF in the normal mode.

Alarm Mode
When a fire alarm condition is detected, the common alarm LED is ON (RED), and the panel is in Alarm
Mode. If the alarm occurs while in trouble or supervisory mode, the panel displays the system trouble LED
steady ON, and silences the trouble buzzer. The trouble relay continues to indicate panel trouble. Zone
Trouble and Supervisory LEDs not in conflict with the alarm LEDs remain ON.

WARNING

Do NOT silence fire signals until certain that a fire condition does not exist.

In the alarm mode, the Indicating Appliance Circuits operate as programmed. The system alarm LED turns
on, the alarm relay operates, and the Relay/City-Tie Module transmits a fire alarm condition, if so
configured. The red IDC zone LED lights, indicating the area of the alarm. The appropriate alarm zone
LED on the Remote Annunciator operates via the Annunciator Driver Module. The dialer will transmit a
zone specific alarm signal to the Central Monitoring Station.

To silence the Indicating Appliances, press the

ALARM SILENCE

switch. Indicating Appliance Circuits will not

respond to the

ALARM SILENCE

switch until all waterflow zones are no longer in the active alarm condition.

Reactivation of the waterflow zone will reactivate the IACs.