Edwards Signaling 2400 Series User Manual

Page 53

Advertising
background image

45

Battery Calculation Example #4
A panel with a Two Zone Initiating Device Circuit Module is to be installed in accordance with the
Canadian National Building Code (NBC) requirement of 24 hours standby, 30 minutes alarm. The
Indicating Appliance Circuit requires 2.5 Amps, and there is no auxiliary power used. Calculate the
minimum required battery capacity that will meet these requirements.

Description

Quantity

Supervisory

(mA)

Total Supervisory

(mA)

Alarm

Total

Alarm

Base Panel

1

x

55

55

100

100

2 Zone input module

1

x

16

16

45

45

Relay Modules

x

16

76

Style D IDC Converter

0

0

40

Dialer

x

12

25

Annunciator Master

x

10

100

Remote Trouble Unit

x

10

10

Auxiliary Power (mA)
Number of Detectors

20

0.050

1.0

1.0

Signal Load (mA)

2,500

TOTAL

72

(A)

2,646

(B)

Battery Calculation
Supervisory Hours

24

(C)

Alarm Minutes

30

(D)

Enter the data in the formula and solve the equation.

attery Capacity (A.H.) =

( .

)+ ( .

)

111

0 033

1000

Ч

Ч

Ч

Ч

=

72 24

2,646 30

4.5 A. H.

NOTE: Battery capacity of panel can be extended to 10 AH using the 2400-BATBOX Battery Cabinet.

Two 12 V, 6.5 AH batteries (P/N 12V6A5) will adequately power this system. Note that this is the same
sample problem as Example #1. In this case, the answer provided by using the worksheets is the same as
the answer provided by using the tables.