ULC Compatibility Listings
Compatible devices listed in this section are for use in CANADA ONLY.

Table 10.9 - ULC Control Unit Compatibility Specifications - Edwards

Electrical Data

Device

ULC Smoke

Detector

Compatibility ID

Standby

Voltage @

Detector

Ripple

Voltage

Maximum Standby Detector Load

EOL

Style B

Style D

2412

2 zone-3 space

panel

0.0

17.85 -26.4 VDC

400 mV

2.5 mA @ 22.3 VDC

N/A

4.7K

P/N EOL-P1

2414

4 zone-2 space

panel

0.0

17.85 -26.4 VDC

400 mV

2.5 mA @ 22.3 VDC

N/A

4.7K

P/N EOL-P1

2418

8 zone-3 space

panel

0.0

17.85 -26.4 VDC

400 mV

2.5 mA @ 22.3 VDC

N/A

4.7K

P/N EOL-P1

2400-2IDC

2 Zone IDC

Module

(P/N 240457)

0.0

17.85 -26.4 VDC

400 mV

2.5 mA @ 22.3 VDC

N/A

4.7K

P/N EOL-P1

2400-BPA

Base Panel Class

A Converter

(P/N 46199-1072)

0.0

17.85 -26.4 VDC

400 mV

N/A

2.5 mA @

22.3 VDC

N/A

2400-IDCA

IDC Converter

(P/N 46199-1074)

0.0

17.85 -26.4 VDC

400 mV

N/A

2.5 mA @

22.3 VDC

N/A

Table 10.10 - ULC Compatible Receivers for the DL1 Dialer Module

Model

Manufacturer

Location

685

Alarm Device Manufacturing Co.,
Div. of Pittway Corp.

Syosset, NY 11791

CP220

Fire Burglary Instruments,
Div. of Pittway Corp.

Syosset, NY 11791

Quick Alert II

Osborne - Hoffman Inc.

Point Pleasant Beach, NJ 08742

D6500

Radionics Inc.

Salinas, CA 93912

9000

Silent Knight Security Systems,
Div. of Willknight Inc.

Maple Grove, MN 55369