3. Electrical Ratings

24 VDC

Must be power-limited.

Current Draw from 24 VDC Input @ Normal Standby: 0.030 amps

Maximum current with all output relays activated: 158 mA.

Relay Contacts

UL contact ratings are 5 amps @ 125 VAC (resistive) or 30 VDC (resistive)
and 2 amps @ 125 VAC (inductive).

Data Communications Port

Must be power-limited.

EIA-485 operating at: 20 Kbaud

Power Requirements

Each ACM-8RF relay module must be accounted for in the power calculations
outlined in the respective FACP installation manual. The ACM-8RF draws its
power from the control panel and must be considered when calculating the
primary and secondary power supply requirements for the system. However,
if the current draw dedicated to the ACM-8RF must be calculated as a separate
figure (in cases where a separate UL listed power source is used), use the
equations below:

Table 3 Power Requirement Calculations

Standby Current

Number of ACM-8RF modules

[ ]

X 0.030

= [ ] amps

Alarm Current

1.) Number of ACM-8RF modules

[ ]

X 0.030

= [ ] amps

2.) Maximum number of relays which

can be activated simultaneously

1

1. The maximum number of simultaneously activated relays depends on system

configuration and programming.

[ ]

X 0.016

= [ ] amps

Total Alarm Current (sum of 1 & 2)

= [ ] amps