Appendix A: MS-5210UD

Application Example #4

28

ACM-8RF PN 50362:C 03/21/01

Application Example #4

Two LED-10 Annunciators, 10 Alarm Only Relays and 20
Alarm/Trouble Relays (no system status relays)

Program the MS-5210UD at Level 3 addresses 02 - 03 for the proper address
setting. The address selected must be the highest or maximum address value
selected on any annunciator or ACM-8RF connected to the EIA-485 port.
(Refer to the Programming Section of the MS-5210UD Instruction Manual).

For this example, only one relay per MS-5210UD zone is required for the first
set of Alarm Only Relays, two relays per MS-5210UD zone is required for the
second set of Alarm and Trouble Relays and the ACM-8RFs are sharing the
EIA-485 bus with two LED-10s. Since ACM-8RFs are sharing the bus with
two other devices, the address setting for the first set of ACM-8RFs should be
switches SW1 = 0 and SW2 = 3 for address '03'. The address setting for the
second set of ACM-8RFs should be switches SW1 = 0 and SW2 = 4 for address
'04'. Enter this highest address into the MS-5210UD Level 3 addresses 02 - 03.

Continued on the next page...